Home > Products > CM 2GF Monitor and Control


The Problem

  • Centralized control and monitoring of the heat trace system.
  • Real time, automatic monitoring of each heating cable's electrical functions.
  • Need to dramatically reduce maintenance costs.
  • Need to reduce problem response time.

Solution

Selecting the CM-2GF allows plant personnel to verify actual installed load current values and perform preventative maintenance by monitoring the actual ground leakage value for each heating circuit. Combining the GF option into the CM-2 totally integrates the temperature control capabilities of the CM-2 with the most advanced load and ground leakage current monitoring available in the industry today.

Features

GENERAL FEATURES:

  • NEMA 4, 4x, 12 enclosures
  • Wide Operating Range: -40°F to + 130°F ambient
  • Conformal coated circuit boards with gold plated connectors
  • Noise and transient immunity from software filters and time delays
  • No memory loss during power outages; has non- volatile memory
  • Communications port available for RS-485
  • FM and CSA certified for Class 1, Division 2, Groups A, B, C and D

SPECIFIC CM-2GF FEATURES:

  • Adjustable ground fault leakage alarm - 1 to 100MA.
  • Adjustable ground fault trip level - 1 to 100mA.
  • Actual ground leakage current read out
  • Programmable high and low current alarms
  • Actual load current read out
  • Easy retrofit into existing CM-2/1 installations
  • Complies with NEC Article 427-22 for ground fault protection of equipment